Maintenance of MV Circuit Breakers
Sep 07, 2017

Maintenance Of Meduim Voltage Circuit Breakers


Maintenance Procedures For:


Medium Voltage Air Circuit Breakers


The following suggestions are for use in conjunction with manufacturer’s instruction books for the maintenance of medium voltage air circuit breakers:


Clean the insulating parts including the bushings.

Check the alignment and condition of movable and stationary contacts and adjust them per the manufacturer’s data.

See that bolts, nuts, washers, cotter pins, and all terminal connections are in place and tight.

Check arc chutes for damage and replace damaged parts.

Clean and lubricate the operating mechanism and adjust it as described in the instruction book. If the operat­ing mechanism cannot be brought into specified tolerances, it will usually indicate excessive wear and the need for a complete overhaul.

Check, after servicing, circuit breaker to verify that contacts move to the fully opened and fully closed positions, that there is an absence of friction or binding, and that electrical operation is functional.


Medium Voltage Oil Circuit Breakers


The following suggestions are for use in conjunction with the manufacturer’s instruction books for the maintenance of medium-voltage oil circuit breakers:


Check the condition, alignment, and adjustment of the contacts.

Thoroughly clean the tank and other parts which have been in con­ tact with the oil.

Test the dielectric strength of the oil and filter or replace the oil if the dielectric strength is less than 22 kV. The oil should be filtered or replaced whenever a visual inspection shows an excessive amount of carbon, even if the dielectric strength is satisfactory.

Check breaker and operating mechanisms for loose hardware and missing or broken cotter pins, retain­ ing rings, etc.

Adjust breaker as indicated in instruction book.

Clean and lubricate operating mechanism.

Before replacing the tank, check to see there is no friction or binding that would hinder the breaker’s operation. Also check the electrical operation. Avoid operating the breaker any more than necessary without oil in the tank as it is designed to operate in oil and mechanical damage can result from excessive operation without it.

When replacing the tank and refilling it with oil, be sure the gaskets are undamaged and all nuts and valves are tightened properly to prevent leak­ age.


Medium Voltage Vacuum Circuit Breakers


Direct inspection of the primary contacts is not possible as they are enclosed in vacuum containers. The operating mechanisms are similar to the breakers discussed earlier and may be maintained in the same manner. The following two maintenance checks are suggested for the primary contacts:


Measuring the change in external shaft position after a period of use can indicate extent of contact erosion. Consult the manufacturer’s instruction book.

Condition of the vacuum can be checked by a hipot test. Consult the manufacturer’s instruction book.